Abstract

<span>Distance relay is prone to mal-operate during power swing, thus most of modern distance relay design is equipped with power swing blocking scheme to block the operation during power swing and reset the blocking operation whenever a fault occurs during power swing. However, the detection of fault during power swing especially for high resistance fault possess a challenging task, therefore it may cause the unblocking function to vulnerable to operate. This paper presents the development of a detection scheme for detecting fault during power swing in test system interconnected with Distributed Generation (DG). In this study, the detection scheme is proposed based on S-Transform analysis on the distance relay input voltage signal. It is demonstrated that the proposed S-Transform detection based scheme can effectively detect various type of fault during power swing includes high resistance fault, as well as able to operate correctly even with the presence of DG in the test system.</span>

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.