Abstract

Frequency Domain Spectroscopy (FDS) is mainly used to determine the moisture in the paper-oil insulation systems in power transformers and Oil-Impregnated-Paper (OIP) bushings. Another application of this method is detection of puncture developing in the paper layer between the adjacent conductive foils in the condenser core. The paper presents theoretical calculations of tanδ frequency response in the case of short circuit of conductive layers in bushing's condenser core and their experimental verification, with the help of paper-oil insulation capacitor. Furthermore, examples of measurements of real bushings in operation that agree with the proposed idea are described.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.