Abstract
Summary This paper presents a new improved detailed model for transformer windings. This model accurately represents the transient behaviour of transformer winding better than does the conventional detailed model. The dominant resonance frequencies can be identified using the conventional model; however, nondominant resonance could not be detected. The proposed model can detect both dominant and nondominant resonance frequencies. Frequency response analysis was applied to a 20/0.4 kV 1600 kVA transformer. The simulation results obtained by the conventional and proposed models were compared with the measurement results. The results show the ability of the improved version to model dominant and nondominant resonance. A heuristic method is also proposed to overcome the problem of estimating parameters in large-scale models.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: International Transactions on Electrical Energy Systems
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.