Abstract

Voltage sag is one of the common cause for mal operation of most the equipment. This paper presents an algorithm to detect and classify voltage sag causes based on Empirical Mode Decomposition (EMD). EMD is a method which decomposes a non stationary signal into different mono component signals. These mono component signals are called Intrinsic Mode Functions (IMFs). The magnitude plot of the Hilbert Transform (HT) of the first IMF has the ability to detect the disturbance. The features of the first three IMFs of each disturbance are used as inputs to Probabilistic Neural Network (PNN) for identification of voltage sag causes. Three voltage sag causes are (i) Fault induced voltage sag (ii) Starting of induction motor and (iii) Three phase transformer energization. A comparison is made with wavelet transform. Simulation results show that the EMD method is more efficient in classifying the voltage sag causes.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call