Abstract

Estimating power system states accurately is crucial to the reliable operation of power grids. Traditional weighted least square (WLS) state estimation methods face the rising threat of cyber-attacks, such as false data injection attacks, which can pass the bad data detection process in WLS state estimation. In this paper, we propose a new detection method to detect false data injection attacks by tracking the dynamics of measurement variations. The Kullback–Leibler distance (KLD) is used to calculate the distance between two probability distributions derived from measurement variations. When false data are injected into the power systems, the probability distributions of the measurement variations will deviate from the historical data, thus leading to a larger KLD. The proposed method is tested on IEEE 14 bus system using load data from the New York independent system operator with different attack scenarios. We have also tested our method on false data injection attacks that replace current measurement data with historical measurement data. Test results show that the proposed approach can accurately detect most of the attacks.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.