Abstract

AbstractInfrared thermography of brazed plate heat exchangers for evaporators and condensers recently was used to quantify maldistribution. With the knowledge of the secondary fluids heat transfer coefficient and a given secondary fluids distribution, the local heat transfer coefficient of the primary fluid (refrigerant) and its distribution to the channels can be calculated. A sensitivity analysis shows ± 10 % difference of the surface temperature to the wall center temperature at the expected ratios of heat transfer coefficients. The method is presented in this paper using an exemplary infrared picture.