Abstract

Voltage-source-converter (VSC) technologies present a bright opportunity in a variety of fields within the power system industry. New modular multilevel converters (MMCs) are expected to supersede two- and three-level VSC-based technologies for HVDC applications due to their recognized advantages in terms of scalability, performance, and efficiency. The computational burden introduced by detailed modeling of MMC-HVDC systems in electromagnetic-transients (EMT)-type programs complicates the study of transients especially when these systems are integrated into a large network. This paper presents a novel average-value model (AVM) for efficient and accurate representation of a detailed MMC-HVDC system. It also develops a detailed 401-level MMC-HVDC model for validating the AVM and studies the performance of both models when integrated into a large 400-kV transmission system in Europe. The results show that the AVM is significantly more efficient while maintaining its accuracy for the dynamic response of the overall system.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.