Abstract

An experimental investigation on design of a vapour absorption system using LiBr-H2Ofor high grade heat recovery in thermal cooling system for process heat applications has been conducted. A 1.5 kW cooling capacityof the LiBr-H2O vapour absorption system has beend esigned and tested under various operating conditions. Generator temperature, absorber tem-perature, condenser temperature and evaporator temperature have been varied and perfor-mance of LiBr-H2O vapour absorption system has been analysed. Experimental results are presented in terms of COP and circulation ratio. Further, to validate the results thermody-namic model is developed using first law of thermodynamics and simulate in Engineering Equation Solver. The COP and the circulation ratio estimated through simulationsand exper-iments have been in good agreement with ±5% standard deviation. Further, this this research work is beneficial for dairy industries in process heat applications and realizing the impor-tance of the need for energy conservation in dairy industries.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.