Abstract

AbstractA new approach is presented to overcome load disturbance problems. Based on the parallel cascade control structure, the primary controller is designed for the servo response, and the secondary controller is designed for the disturbance‐rejection purpose. A perfect disturbance‐rejection controller is derived for the secondary loop. Simulation studies show that improvement in load responses can be achieved for some cases. However, for some other cases, parallel cascade control simply worsens the load responses as a result of interaction between primary and secondary loops. A new interaction measure for load disturbance (γ) is proposed to determine whether improved load responses is achievable using cascade control structure. More importantly, the interaction measure also quantifies the margin of improvement that can be achieved over conventional single‐loop control. A design procedure for improved load responses was proposed. The simulation results show that the new approach offers a simple and effective alternative for disturbance‐rejection.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.