Abstract

Steady-state, harmonics, and transient analysis of a power system by using a detailed simulation model is essential to microgrid operation before the installation of new power facilities, because the microgrid, which is a small-scale independent power grid consisting of distributed resources and an energy storage system, has no choice but to include many inverters consisting of switching devices. Accordingly, in the case of an accident in a microgrid system, various power system simulation tools must be used to calculate the fault current for grid protection components. Specifically, Modelling using Power System Computer Aided Design (PSCAD)/Electro-Magnetic Transient Design and Control (EMTDC) can perform detailed modeling of switching devices into each inverter, and Electrical Transient Analyzer Program (ETAP) can design protection relays. From this perspective, this study designed whole protection components in a microgrid system, including the capacity of switching devices for fault ride through a protective relay and the capacity of the circuit breaker. The parameters of an actual microgrid on the San Cristobal Island, Galapagos, were used to make a detailed simulation model in both PSCAD/EMTDC and ETAP. The capacities of the switching devices were estimated by using PSCAD/EMTDC. Additionally, the rated breaking capacities and the setting values of the protective relay were also calculated from the result of an ETAP simulation.

Highlights

  • According to advanced research, computer modeling and power system analysis are very important for the stable operation and management of power systems [1]

  • In order to confirm the result of the system accident through Power System Computer Aided Design (PSCAD)/Electro-Magnetic Transient Design and Control (EMTDC), it is assumed that a single line ground fault occurred in about 5 s

  • We proposed a complete protection system of a microgrid using the PSCAD/EMTDC

Read more

Summary

Introduction

Computer modeling and power system analysis are very important for the stable operation and management of power systems [1]. Before connecting a new power facility to a sensitive power system such as a microgrid, detailed analysis using computer simulation must be performed to check normal operation, transient state, harmonics, and dynamic characteristics. As the microgrid is a small-scale independent power grid, which consists of renewable energy sources, such as solar or wind power, with an energy storage system (ESS), a detailed power system analysis should be completed [2,3]. Several inspiring papers, such as ”Fault analysis of. Detailed modeling of the inverter switching device and the conventional

Results
Discussion
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.