Abstract
A two-phase loop thermosyphon system is developed for the B-ISDN telecommunications system and its performance is evaluated both experimentally and by visualization techniques. The design of the thermosyphon system proposed is aimed to cool muliichip modules (VICM) upto heat flux of 8 W/cm 2 . The results indicate that in the loop thermosyphon system, cooling heat flux is capable of 12 W/cm 2 with two condensers under the forced convection cooling of the condenser section with acetone or FC-87 as the working fluid. The instability of the working fluid flow within the loop is observed using the visualization techniques and temperature fluctuation is stabilized with orifice insertion.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.