Abstract

A facility for submicron VLSI chip manufacturing has been designed with the concept of the SMIF (standard mechanical interface) optimized cleanroom system. This facility involves an 80000 square foot cleanroom with a class 1000 ambient nonlaminar air flow, with equipment isolated in subclass 1 islands, each with SMIF interfaces. Significant reduction in the clean air requirements resulted in a reduction in air handling requirements, thereby leading to reduced construction and operating costs. Isolated subclass 1 islands provide assured cleanliness even in the event of external contamination disturbances. In effect, class 1 is assured immediately above the exposed wafers in such a facility as compared to at-the-ceiling as in a conventional cleanroom. Facility design concepts and estimates of cost savings in facility construction and operation are presented. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.