Abstract
Objective of this research was to design, construction and test of a cold store with chiller unit. Dimensions of the cold store were 5x4x3m. Heat load was calculated and capacity of cooling system was determined. Ambient temperature was set 2oC and relative humidity 90% for cold store testing. Ambient temperature, relative humidity and air velocity were measured for 3 different levels and 12 points for each level in the cold store. Total heat load and capacity of cooling system were calculated 5222 kcal/h. and 6.07 kW respectively. The descriptive statistics were calculated for the ambient temperature; mean, 2.82oC, standard deviation 0.02oC and CV(%) 0.56, and for the relative humidity; mean 88.01%, standard deviation 0.61 (%) and CV(%) 0.70 and for the air velocity mean 0.37m/s, standard deviation 0.22 m/s, CV 33.45 %. Even the air velocity CV was high, the ambient temperature and relative humidity variations were evaluated very good.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: Latin American Applied Research - An international journal
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.