Abstract

A segmented single-artery heat pipe was studied. The work specifically focused on venting of the noncondensable gas-supported vapor blockage in the liquid artery. The successful operation of the heat pipe requires a careful sizing of the venting holes placed on the fine arterial mesh. The two important design parameters, namely, the venting hole diameter and the distance separating the holes, were analyzed by taking into account the required trade-offs. An arterial heat pipe satisfying the sizing criteria was tested at horizontal and adverse elevations at varying heat loads. The measured heat transfer limit and thermal resistance of the pipe demonstrated effectiveness of the design. The pipe performance continuously degraded at adverse elevations.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.