Abstract
This article designs, builds, and tests the 850-V 100-kW 16-kHz bidirectional isolated dc–dc converter using the latest 1.2-kV 400-A SiC- mosfet /SBD H-bridge modules, with focus on efficiency improvement. Here, SBD stands for Schottky barrier diode. It proposes intermittent operation with continuous-current mode (CCM), to reduce switching losses in partial loads. Experimental results verify that the conversion efficiency from the dc input to the dc output is as high as 99.3% at the rated power of 100 kW, and 99.2% at a partial load of 10 kW. These are measured and calculated, discarding auxiliary power losses of 82 W in total, which are produced by the digital controller, gate-drive circuits, and cooling fans. Experimental transient waveforms show that no dc magnetic flux is included in the 850-V 100-kW 16-kHz transformer at intervals of switchover between the continuous operation and the CCM intermittent operation when power reversal from $-$ 100 to 100 kW is performed at an interval of 1 ms. Finally, this article presents an experimental and theoretical discussion on the voltage ripples appearing across the dc capacitor of each bridge.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.