Abstract

This paper presents the detailed engineering study conducted to design a high-impedance restricted earth fault (REF) scheme for four 11/0.415-kV, Dyn11, and 2500-kVA power transformers in an industrial power system. Analytical calculations carried out to specify the components constituting the REF scheme and to determine the appropriate relay settings are provided. The proposed REF scheme is evaluated using reliable Alternative Transients Program–Electromagnetic Transients Program simulations. The obtained results validate the adequacy of the design and highlight the advantages of using such a protection, such as fast and reliable operation even under severe current transformer saturation conditions.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.