Abstract

Flood levels exceeding 2 metres above ground level has been observed causing electrical equipment in the 11/0.415kV substation to be fully submerged. This caused widespread supply disruption as the equipment need to be switched off due to safety reasons and prevention of further equipment damage. The use of submersible equipment and accessories has been identified as one of the mitigation methods to ensure continuous electrical supply during flood events. A research project was undertaken to develop the design criteria of the selection of submersible equipment and accessories as well as to develop the test method and evaluate the selected submersible equipment and accessories in a substation configuration. All the equipment could continuously operate in ON condition during the wet test. However, design improvements are suggested for the submersible switchgear and feeder pillar for better performance during and after flood events.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.