Abstract

A design method for precast concrete buckling-restrained braced frames with traditional gusset plate connections has not yet been codified. In addition, experimental data for this novel system are lacking. The primary objectives of this research were to design and experimentally test a partial system under representative seismic loads and to determine the applicability of the uniform force method (UFM) for connection interface force distribution. A quasi-static cyclic test was performed on a scaled, partial system. Experimental results showed that the UFM alone does not accurately predict interface forces for this system because the method does not account for frame action. Results also showed that there is some change in column base fixity as the frame undergoes larger horizontal displacements. This was the first U.S. laboratory test on a scaled, partial version of this system. Development of a codified design method would require further testing to determine an appropriate interface force distribution and quantify the change in column base fixity.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.