Abstract

Photovoltaic (PV) air conditioning (AC) is an effective way to solve the problems of energy consumption of office buildings. In this study, a set of parameters were designed for PV AC, including PV capacity, AC parameter, and inverter parameter. Then, the parameters were applied to a 20-m2 office building, and a PV AC system test platform was built. The test lasted for one year; the corresponding data including typical daily data and annual data were collected and analyzed. The results show that the PV AC system quickly decreases or increases the room temperature by ~9.5% and 17% in 1 h of cooling and heating periods, respectively, thus maintaining the room temperature within the set temperature range of ±0.9 °C. The data also show that by proper design of parameters, a PV AC system can satisfy the electricity demand of AC. In the cooling period, heating period, and annual operation conditions, the PV system provided 114%, 73%, and 188% of the energy for the AC system, respectively. Next, economic calculations show that PV AC is suitable for office buildings. The local payback period is only 7.5 years; both the energy saving and emission reduction are significant.