Abstract

We predicted the impact of desiccant degradation on the performance of an open-cycle desiccant cooling system in ventilation mode using the degradation data on silica gel obtained from a previous study. The degradation data were based on thermal cycling desiccant samples and exposing them to ambient or contaminated air. Depending on the degree of desiccant degradation, the decrease in the thermal coefficient of performance (COP) and the cooling capacity of the system for low-temperature regeneration was 10 percent to 35 percent. The 35 percent loss occurred based on the worst-case desiccant degradation scenario. Under more realistic conditions the loss in system performance is expected to be lower.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.