Abstract

The influence of natural aging furthered by atmospheric corrosion of parts of electric transformers and materials, as well as of concrete poles and cross arms containing corrosion inhibitors was evaluated in Manaus. Results for painted materials, it could showed that loss of specular gloss was more intensive in aliphatic polyurethane points than in acrylic polyurethane ones. No corrosion was observed for metal and concrete samples until 400 days of natural aging. Corrosion in steel reinforcement was noticed in some poles, arising from manufacturing faults, such as low cement content, water/cement ratio, thin concrete cover thickness, etc. The performance of corrosion inhibitors was assessed by many techniques after natural and accelerated aging in a 3.5% saline aqueous solution. The results show the need for better chemical component selection and its concentration in the concrete mixture.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.