Abstract

Operational parameters of air handling units (AHUs) play an important role in the energy and comfort performance of commercial buildings. Current guidelines to determine these parameters are based on heuristics and are not informed by formal optimization. This paper presents a building performance optimization method to derive sequence of operations for multi-zone AHUs. To this end, 27 variants of a generic EnergyPlus office building model are built representing three levels of occupancy, envelope, and HVAC capacity scenarios. The supply temperature, morning start time, and economizer settings of the model are optimized for the 27 scenarios by using a genetic algorithm. The results highlight that optimal supply temperature setpoints transition from ∼12°C to a range of ∼16°C to ∼20°C over an outdoor temperature range of ∼20°C to ∼0°C. Energy savings are estimated as ∼20% relative to a reference case with a constant supply temperature and preheating/precooling period.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.