Abstract
This paper presents a method for determining the load capacity of three-phase squirrel-cage induction motors supplied with a balanced distorted voltage containing rotating harmonics (1st, 5th, 7th, 11th, 13th,...). The method is based on the dependence of the motor load capacity on the load power losses in the rotor cage. The load capacity was determined based on motor short-circuit measurements made for frequencies equal to harmonic frequencies. To evaluate the load capacity, a factor with the proposed name Harmonic Losses Factor (HLF) was introduced. Its expression is a generalization of the well-known HVF expression. However, it has been shown that a more accurate estimation of the load capacity is obtained using the sum of load power losses in the rotor cage from higher harmonics. Measurements and calculations were carried out for a low-voltage squirrel-cage motor with a rated power of 22 kW and a synchronous speed of 1500 rpm. Calculations showed that the derating power curves given in the IEC 60034-17 and NEMA MG1 standards are incorrect for the tested motor.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.