Abstract

According to building regulations, fire dampers should be installed in or close to the part of the duct that penetrates the fire compartment. Accordingly, in construction sites, fire dampers are installed in or adjacent to the fire compartment wall and floor. However, they are often installed too far away from the fire compartment wall and floor because the law does not stipulate a clear standard for “close”. If this occurs, the duct and sleeve in the spaced part may be transformed by the high heat of a fire. Through this, smoke and flames can be directly transmitted to the neighboring compartment space, failing to ensure fire safety. Therefore, this study investigated the dependence of fire safety on the spaced installation of fire dampers by performance verification. From the performance verification results, it was found that the separation distance of the fire damper should be minimized (i.e., attached to the wall) to ensure fire safety.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.