Abstract
A DX air cooling coil may normally be assumed to have two regions in its refrigerant side, according to refrigerant status, a two-phase region (TPR) and a superheated region (SPR). Dry air side surface of the SPR in a DX air cooling coil has been normally assumed in lumped-parameter mathematical models previously developed without however being validated. Therefore, an experimental study has been carried out to examine such an assumption under different operating conditions. The experimental results suggested that the air side surface of the SPR in a DX air cooling coil was either fully or partially wet under all experimental conditions and assuming dry air side of the SPR could lead to an underestimated total amount of water vapor condensed on the entire DX coil surface. Therefore, it is recommended that the assumption of dry air side in a SPR be no longer used in future lumped-parameter models to be developed for improved modeling accuracy.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.