Abstract

With a higher share of renewable energies also the control of the grid must be organized by renewable energy generators. Storages are attractive for grid control and especially for primary reserve power. Theoretically, positive and negative frequency deviations should average to zero and charging and discharging of the battery should compensate each other. However, in reality, an offset may appear. Then, the state of charge of the battery quickly exceeds any limits. To avoid this, degrees of freedom are allowed while providing primary reserve power. This publication investigates their effect on the state of charge. It is shown that the compensation of a systematic frequency measurement error by applying a running average correction signal is most effective.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.