Abstract

The factors which affect the performance of mechanical connectors for use on aluminium power cables have been investigated. The initial resistance depends upon surface roughness, mechanical load and degree of plastic deformation. The stability of resistance has been studied under conditions of mechanical-load cycling, stress relaxation, interface oxidation, temperature cycling and current loading. The conditions for designing stable mechanical connectors for use on aluminium conductors are given, and the stability of connectors satisfying these conditions has been illustrated by current-cycling measurements.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.