Abstract
The pressure field in fluid systems reflects the flow configuration. Measurements of the pressure along the perimeter of a slot ventilated room have been conducted for different room sizes. The momentum of the jet at the end of the room is decreased with increasing room length. The impingement region (region where the influence of the opposing wall is present) starts, independent of room size, when the distance from the supply device is about 70% of the room length. Corner flows could not be predicted by CFD using the linear eddy viscosity or standard stress models. However, these effects may be captured by using a second moment closure turbulence model with a new near wall approach now available in literature.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.