Abstract

Due to the increasing penetration of distributed renewable energy generation systems, their participation in power system restoration is gaining a growing interest. For the black start of a system without synchronous generation, Wind Energy Conversion Systems (WECSs) must be able to control voltage and frequency. However, WECSs have been traditionally controlled as current sources. This paper proposes a decentralized control system for the black start of WECSs operating in parallel. In comparison with known methods for operation of distributed energy resources without synchronous generation, this paper specifically addresses the requirements of WECSs. Total wind power is regulated to match the demand during the black start process. This power is shared between WECSs according to the wind power available in each of wind turbine using a droop control characteristic between the voltage and active power. Using the so-called reactive power synchronization method, the WECSs can operate in synchronism even if wind power is significantly different in each wind turbine. Simulation results for a case study where two WECSs are connected in parallel are presented to validate the proposal.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call