Abstract
Resonances can have a negative impact on a voltage-source converter-high voltage dc (VSC-HVDC) system. This paper develops dc impedance models for the rectifier and inverter stations for a VSC-HVDC system when they are viewed from a dc terminal. The impedance models take converter controllers into account. The derived impedance models are validated by comparing frequency responses of the analytical model and the impedance measured at the dc terminal from a detailed VSC-HVDC model simulated in a real-time digital simulator. Resonances are examined in the frequency domain (e.g., Bode plots and Nyquist plots) using the derived analytical impedance models. The analysis is verified by time-domain simulations. Real-time digital simulation in RT-Lab demonstrates that the dc capacitor has a significant impact on resonances while the power transfer level has an insignificant impact on resonances.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.