Abstract
The Kii-Channel HVDC Link under construction in Japan is equipped with metallic return transfer breakers (MRTBs) in one converter station. A new MRTB for an interrupting current of 3500 A DC was developed. To interrupt a DC current, a method that produces a current zero point by superimposing a self-excited oscillatory current on a DC arc current was employed. For this purpose, a LC circuit was coupled in parallel to a SF/sub 6/ gas circuit breaker. Developing a SF/sub 6/ gas circuit breaker that has a large arc voltage drop gradient against currents permitted a large oscillatory current to be generated. A modified Mayr-type dynamic arc equation was newly presented. The DC interruption limits calculated using this equation agreed with the measured values.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.