Abstract

The Kii-Channel HVDC Link under construction in Japan is equipped with metallic return transfer breakers (MRTBs) in one converter station. A new MRTB for an interrupting current of 3500 A DC was developed. To interrupt a DC current, a method that produces a current zero point by superimposing a self-excited oscillatory current on a DC arc current was employed. For this purpose, a LC circuit was coupled in parallel to a SF/sub 6/ gas circuit breaker. Developing a SF/sub 6/ gas circuit breaker that has a large arc voltage drop gradient against currents permitted a large oscillatory current to be generated. A modified Mayr-type dynamic arc equation was newly presented. The DC interruption limits calculated using this equation agreed with the measured values.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.