Abstract

In DC choppers and inverters transformers are employed to recover the trapped energy in the commutating inductors in order to reduce the overvoltage of the commutating capacitors. It is known that the leakage factor of real transformers keeps the overvoltage substantially high. The present work shows that a finite Q-factor of real transformers significantly reduces the overvoltages, resulting in lowering of voltage and current ratings of the components. The proposed modification in the connection of the transformer leads to additional recovery of the trapped energy, resulting in further reduction of overvoltage and commutation loss. This energy recovery process must be completed in the OFF-interval to avoid spikes in the output voltage. Graphs for overvoltages, peak currents, per-unit loss and maximum permissible frequency factor have been plotted for the original and the modified scheme of the DC chopper. Experimental results justify the theoretical analysis.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.