Abstract
This study investigated the impact of well geometry on vertical sky components in atria with square and rectangular forms under a CIE standard overcast sky. By comparing scale model measurements and analytical theory the vertical sky components, calculated using Radiance, were validated. More simulated data of vertical sky components for a very wide range of atrium geometries are given. From the results the attenuation of the vertical sky component on the wall of a square atrium is explained and some empirical functions are derived. In addition, the results from atrium models with rectangular floor plans show the relationships between the vertical sky component and the plan aspect ratio. Some guidelines for design are presented.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.