Abstract
Recently increasing amount of data centers (DCs) have been constructed for the development of information and communications technology (ICT). Meanwhile, more energy consumption is required to support the operation of DCs, where nearly thirty percent of the consumption is used for cooling system. Therefore, this paper studies an efficient cooling architecture named rack mountable cooling unit (RMCU) for DCs, and provides a novel data-driven fault tolerant predictive controller to regulate the temperature accordingly. In order to circumvent the complicated physics modeling in DC, a data-driven modeling method is developed. In this method, multiple local linear models in form of auto-regressive exogenous (ARX) model are selected to describe the strongly nonlinear system. Besides, the multiple sub-models are identified through partial least square (PLS) and corresponding training data is partitioned by fuzzy c-means (FCM). Then, on the basis of developed data-driven model, a predictive controller considering actuator faults is designed to manage the temperature in DC. Finally, real experimental results are presented and demonstrate the superior performance of our proposed controller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.