Abstract

High Voltage Direct Current transmission (HVDC) will cause torsional interaction under certain conditions. Among a variety of factors, improper rectifier control has fateful effect. In the paper, the test signal method which is the time-domain form of the complex torque coefficient approach (CTC approach) is studied. Its application conditions in multi-machine systems are summarized. Using the test signal method, impacts of DC power, DC voltage, rectifier controller parameters and generator output on electrical damping characteristics in the Suizhong system are studied based on time-domain simulation model.