Abstract

The problem of harmonics in electric power system can not be ignored, because with the increasing use of non-linear equipment (eg flouresent lamp), that flouresent lamp can cause harmonics in odd order of multiples of 3 that is equal to 15% , in this research two measurements are measured by using flouresent lamp load and incandescent lamp as comparison. The measurement used in this research is to use the harmonic power analysis instrument. From the result of measurement, it is found that in the experiments on 3 phase 4-wire system when the incandescent lamps are given each phase is balanced, the current in the neutral conductor is 0.08 Amper. While in the second experimental 3 phase 4-wire system when given 2x40 Watt flouresent lamp loads that each phase is balanced, then the current in the neutral conductor becomes excess that is equal to 0.26 Amper. The results of this measurement indicate that the harmonics caused by flouresent lamps are very worrying if the neutral cable carrier used on small-diameter electrical installation network, this could endanger the installation of fire.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.