Abstract
Purpose: Clinical data show that contact lens (CL) multipurpose solutions (MPS) may cause damage to the ocular surface. This study examined the cytotoxic and inflammatory effects of CL MPS and hydrogen peroxide CL disinfection systems (HPCLDS) on cultured human corneal epithelial (HCE) cells.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.