Abstract

A gas-fired absorption heat pump with cooling capacity of 2 RT was analysed as an air-conditioner for domestic use during the summer. The absorption heat pump considered was an air-cooled, double-effect, LiBr/H 2O system of parallel-flow type. The performance of the absorption heat pump in the cooling mode of operation was investigated through cycle simulation to obtain the system characteristics depending on the inlet temperature of air to the absorber, the working solution concentrations, the solution distribution ratio of the mass of solution into the first generator to the total mass of solution from the absorber, and the LTDs (leaving temperature differences) of the heat-exchanging components. When the predicted results were compared with the measured data for similar design conditions, reasonable agreement was observed. The optimum design and operating conditions of an air-cooled absorption system are suggested based on this cycle simulation analysis.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.