Abstract

This paper describes a new approach to select the optimum sinewave pulsewidth modulation (PWM) patterns suitable for a large-capacity current-fed active PWM power converter and a practical design procedure to determine circuit constants of a low-pass filter connected to suppress higher line current harmonics flowing into the utility-grid AC power source. A feasible test is implemented by building a prototype 500 kW three-phase current-fed PWM power converter which is designed and controlled on the basis of the proposed considerations. It is verified from a practical point of view that these new conceptual considerations are more effective and acceptable to minimize higher harmonic current components flowing into the utility-grid AC power source. This experimental setup provides highly efficient steady-state characteristics of the current-fed three-phase PWM power converter under the operating condition of a unity power factor correction and sinewave line current shaping schemes. Furthermore, this unique optimum PWM pattern derived from the theoretical method proposed here is conveniently applicable to a voltage-fed three-phase PWM converter. It is verified that this optimum PWM pattern provides excellent switching performance with a lower switching frequency mode than the conventional carrier-based PWM scheme.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call