Abstract

This paper proposes a partial nonlinear model to accurately represent the nonlinear saturation characteristic of a current transformer (CT). Based on the model, the saturated section of the secondary current as well as the unsaturated section can be used in a regression process to estimate model parameters. The saturated section normally lies near the inception of a fault, therefore accurate parameters can be obtained faster compared with the methods using only unsaturated sections. The pre-fault remanent flux and DC-offset, which could significantly influence CT saturation, are both considered in the model, thus they do not affect the accuracy of the parameter estimation. The computational load of the regression calculation is significantly reduced by using separable nonlinear least squares (SNLLS) method. This provides the feasibility to implement the method for real-time protective relaying. The performance of the method has been evaluated on the data obtained from both PSCAD/EMTDC simulation and live recording with a test CT. The method has also been implemented in a Field Programmable Gate Array (FPGA).

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.