Abstract
Abstract We have proposed new design of a transformer type SFCL with primary and secondary superconducting coils which has rewound structure. For not so large fault current, the proposed SFCL limits the current by the inductive component by the normal transition of the flux shielding coil (secondary), and for larger fault current, it can give the resistive component additively by the normal transition of the primary coil. The recovery characteristics under load condition and repetitive limiting operation were experimentally investigated in a laboratory scale power system. The SFCL limited twice repetitive faults current and recovered quickly under load condition.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.