Abstract

The paper describes a mathematical model to be used in calculating the current distribution among the coils in the low-voltage winding of the furnace transformer. The method is derived from the leakage magnetic-field distribution in the transformer based on the minimum magnetic-field energy. The energy is calculated by using the principle of the minimum reactive power in the transformer window. The results are validated by using the finite-element model. The knowledge of the proper current distribution is very useful in designing the furnace-transformer cooling system to avoid local overheating.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.