Abstract

Non Conventional Instrument Transformer (NCIT) and IEC 61850 are crucial technologies in digital substations. But they bring some new uncertainties to protection IEDs, especially the time synchronization issue in current differential protection. The paper analyzes the time delay of transferring sampled values from NCIT to current differential relay in NCIT and IEC61850 based digital substation, then finds out the delay-non-deterministic problem, at last presents a novel current differential protection scheme by using Phase-Locked Loops (PLL ) technology.