Abstract

The aim of the study was to analyze all current values from measured periods while performing tasks on 400 kV power lines. Our aim was also to study the average current densities and average total contact currents caused by electric fields in 400 kV power line tasks. Two workers simulated the following tasks: (A) climbing up a portal tower, (B) climbing up a portal transposing tower, (C) working on the cross-arm of a portal tower, (D) climbing up a portal tube tower, (E) climbing up a Tannenbaum tower on the side of the energized circuit with the other circuit unenergized, (F) climbing up a Tannenbaum tower with both circuits energized, and (G) climbing up a Donau tower. The highest average current density in the neck was 2.5 mA/m(2) (calculated internal electric field 31.5-63.0 mV/m), and the highest average of the contact currents was 240.0 µA. All measured values at 400 kV towers were lower than the limit value of 10 mA/m(2) in the first version of Directive 2004/40/EC and the basic restrictions (0.1 and 0.8 V/m) of the International Commission on Non-ionizing Radiation Protection.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.