Abstract
This paper presents a study on the double-band hysteresis current controller of the STATCOM (static synchronous compensator) used for reactive power compensation on a distribution network. Hysteresis controllers are intrinsically robust to system parameters, suitable for simple implementation and exhibit very high dynamic response. But in D-STATCOM, the current control using a conventional hysteresis controller has the disadvantage to be high switching frequency. In addition, the current error is not strictly limited. Therefore, in this paper, to reduce the switching frequency and current error, a double-band hysteresis current controller in stationary reference frame is proposed. The proposed double band hysteresis current control system was testified by the Borland C++ program and demonstrates the advantage of the proposed hysteresis current control method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.