Abstract

By applying second-generation FACTS devices, it is possible to improve the quality of the electric power supply, including the balancing of potentially unbalanced voltages. However, in order to be able to analyse such conditions, the procedures for a three-phase, load-flow calculation have to be applied. Therefore, in this article the three-phase, current-based models of FACTS devices for load-flow calculations using the Newton–Raphson method are described. The derived procedures are based on already-developed models for one-phase calculations. Although the principles are the same, there are still some details that had to be investigated, and some additional testing was necessary. The robustness of the method with respect to the initial values is of crucial significance; therefore, special attention was paid to this issue. Finally, two typical tests on IEEE 57 and IEEE 300 bus electrical power systems are presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.