The heating phenomenon of connector terminals in converter stations has become increasingly common, it has become a serious safety hazared affecting the operation of UHV lines. This paper determined the overlapping model of Al plate-Al plate based on the heating phenomenon of connector terminals in converter stations, conducted the tests which included disassembly and assembly contact surface roughness impact test, pressing force impact test, operation impact test, electric composite grease impact test, anti-loosening measure impact test. Analyzed the main influencing factors of current and temperature-rise for connector terminals heating, and analyzed the influence rule of each factor for current and temperature-rise of connector terminals. Test shows that: bolt tightening torque and electric composite grease was the main influencing factors for current and temperature-rise of connector terminals, and bolt tightening moment was the first main factor, bolt looseness and the performance degradation of electric composite grease directly causes an increase in the contact resistance and temperature rise level of the connector terminals.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.