Abstract

The draft Long-Term 2 Enhanced Surface Water Treatment Rule (LT2ESWTR) contains Cryptosporidium log-inactivation CT tables (ozone-in-water concentration [residual], “C” times contact time, T). Depending on water temperature, Cryptosporidium CT values that are listed are 15 to 25 times greater than CT values for equivalent Giardia log-inactivation credit. The elevated operating dose required for Cryptosporidium log-inactivation credit has the potential to increase disinfection by-product (DBP) formation (e.g., bromate). Calculating CT value accurately will minimize ozone dose, which will decrease operating cost and lower DBP formation, and at the same time maintain disinfection protection through implementation of scientifically based safety factors. Various methods are available for calculating CT value. The method chosen depends largely on the available information concerning ozone residual characteristics and hydrodynamic features of the ozone contactor, plus local regulatory requirements. Four methods are discussed in this paper. Each method can be used to calculate Giardia, virus, and Cryptosporidium log-inactivation credit.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.