Abstract

This report describes the selection of the relief valves for the D-Zero cryostats. The selection was based on the flow requirements calculated in D-Zero engineering note 3740.214,224-EN-6 under fire conditions (1200 F, no vacuum) for the central cryostat; 264 SCFM. This value was calculated from section 5.3.5 of 'Pressure Relief Device Standards; S 1.3-Compressed Gas Storage Containers', published by the Compressed Gas Association, Inc. The flow calculated above is far greater than the required fire condition flow capacity of 264 SCFM. The improbable 70 F flow temperature value of 738 SCFM is still much greater than the required fire capacity. The flow capacity of the paralleled supplemental rupture disc is 2640 SCFM, independently greater than the fire condition flow requirement.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.