Abstract

Where water shortage is concerned, air-cooled chillers are typically installed to provide cooling energy in commercial buildings with significant electricity consumption. This study investigates performance data and technical specifications on a wide range of air-cooled chiller products. The coefficient of performance (COP) of the chillers at full load operation ranges from 2.4 to 3.7, with 2.9, 3.1 and 3.3 in the 25th, 50th and 75th percentiles, respectively. A survey on national standards and guidelines for the energy performance of air-cooled chillers shows that the minimum required COPs lie between 2.4-3.1 at full load operation. This suggests that over 50% of the existing products can meet the requirement and more stringent control should be in place to boost the use of high efficiency chillers. Control algorithms should be further exploited to judge if the chillers operate with desirable performance under part load conditions. Advanced controls are seldom applied to optimize their performance at part load operation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.